Discover LG CANADA HVAC

Air Source Units
Multi V Space II

Multi V Space II

Power Supply: 208-230V / 60Hz / 1ø

Consult your Rep for pricing

PRODUCT SUPPORT

LG Multi V Space VRF is a Heat Pump system that is a single phase 4.4 ton outdoor unit which can be linked to up to 9 indoor units using a single refrigerant piping system. It uses factory designed and supplied Y-branches and headers, and has integrated controls. The LG Multi V Space Heat pump system can operate in either cooling or heating mode.

  • Provides VRF system zoning and efficiency
  • Rear side air intake / air discharge
  • Suitable for indoor installation behind a louver
  • Compact size for installation
  • Operating ranges of 23°F to 118°F in cooling mode
  • Quiet and comfortable environment
  • Reduced ductwork

Available models: ARUN053GF2

Model   ARUN053GF2

Ton  4.4

 

 

Capacity

Cooling

Btu/h

53,000

Heating

Btu/h

59,000

Power Supply

V/Hz/ø

 

208-230 / 60 / 1

Dimensions(W×H×D)

inch

29 1/2 x 70 1/2 x 25 1/2

Net Weight

lbs

 

320

Casing Color

 

 

Warm Gray

Sound Pressure* (Rear Fan Side / Front)

dB(A)

 

68 / 53

 Fan

Type

Propeller fan

 

Air Flow Rate(High)

cfm

3,532

Compressor

Type

 

DC Inverter Rotary

 

Number of compressors

1

Heat Exchanger

Rows / Fins per inch

 

2 / 14

Refrigerant

Refrigerant Type

R410A

Charge

lb

7.7

 

Control

 

EEV / Indoor Unit

Maximum Number of Indoor Units

 

* Sound pressure levels as tested in an anechoic chamber under ISO Standard 3745.

Note :
1. Capacities are nominal (outside the scope of AHRI Standard 210/240) based on the following conditions
    Cooling-Indoor temp. 80°F DB / 67°F WB                    Heating-Indoor temp. 70°F DB
    Outdoor temp. 95°F DB                                           Outdoor temp. 47°F DB / 43°F WB
    Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft(7.5m)
    Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Sound pressure levels as tested in an anechoic chamber under ISO Standard 3745. Due to our policy of innovation some specifications may be changed without notification.

 

Download Type Category Product Name Model No.
Download Submittals Air-source Multi V Space II ARUN053GF2
Download Engineering Manuals Air-source Multi V Space II NA
Download Installation Manuals Air-source Multi V™ Space II NA
Download BIM / REVIT Air-source NA
Download 2D CAD Models Air-source NA
Download Product Warranty Warranty Card 2/7 Multi V™ IV, Water IV, Space II, Indoor Units, DOAS & ERV NA
Download Brochures Air-source NA