Discover LG CANADA HVAC

Discontinued Products
Multi V III Heat Recovery 208-230V

Multi V III Heat Recovery 208-230V

Power Supply: 208-230V / 60Hz / 3ø

Model No.: ARUB072BT3

Consult your Rep for pricing

PRODUCT SUPPORT

This new technology product line is LG’s premiere VRF system. The third generation of the popular Multi V VRF series, Multi V III features higher energy efficiency and longer piping capabilities. Multi V III has enhanced energy efficiency and is ARHI 1230 certified. Multi V III is designed to provide the owner the benefit of VRF - lower operational costs minimal or no duct work to install, tenant comfort with individual zoning, efficiency superior to other technologies while maintaining architectural integrity with zoned comfort.

•    Available in 208-230V & 460V with sizes ranging from 6 - 36 tons
•    AHRI 1230 certification for Multi V III VRF
•    Enhanced energy efficiency
•    New LG inverter scroll high side shell design
•    Eliminates the need for a cooling tower or water maintenance
•    Compact size footprint where space is a premium
•    Longer piping distances
•    Dual compressors in larger models

Available models: ARUB072BT3, ARUB096BT3, ARUB121BT3, ARUB144BT3, ARUB168BT3, ARUB192BT3, ARUB216BT3, ARUB240BT3, ARUB264BT3, ARUB288BT3, ARUB312BT3, ARUB336BT3, ARUB360BT3, ARUB384BT3, ARUB408BT3, ARUB432BT3,

Model  ARUB072BT3

Single Frame

   

Ton  6

 

 

 

Capacity

Cooling

Btu/h

72,000

 

Heating

Btu/h

81,000

Power Supply

V/Hz/ø

 

208-230 / 60 / 3

Dimensions(W×H×D)

inch

 

36 1/4 x 66 1/8 x 29 15/16

Net Weight

lbs

 

418

Casing Color

 

 

Warm Gray

Sound Pressure*

dB(A)

 

57

Fan

Type

 

Propeller fan

 

Air Flow Rate(High)

cfm

6,300

Compressor

Type

DC Inverter Scroll

 

Number of compressors

1

Heat Exchanger

 

 

GoldFinTM

Refrigerant

Refrigerant Type

R410A

 

Charge

lb

12.1

 

Control

 

EEV

Maximum Number of Indoor Units

 

13

       

* Sound pressure levels as tested in an anechoic chamber under ISO Standard 1996.

       

Note :
1. Capacities are nominal (outside the scope of AHRI Standard 1230) based on the following conditions
    Cooling-Indoor temp. 80°F DB / 67°F WB               Heating-Indoor temp. 70°F DB
    Outdoor temp. 95°F DB                                Outdoor temp. 47°F DB / 43°F WB
    Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft(7.5m)
    Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. When the calculated refrigerant charge is over 209lb(95kg), multiple outdoor system must be divided into smaller independent systems. So, each system contains less than 209lb(95kg) refrigerant charge.

 

Download Type Category Product Name Model No.
Download Product Warranty Warranty Card 2/6 Multi V S, II, III & Mini NA