Discover LG CANADA HVAC

Discontinued Products
4 Way Cassette 3'x3' Chassis TNC2/TMC2

4 Way Cassette 3'x3' Chassis TNC2/TMC2

Power Supply: 208-230V / 60Hz / 1ø

Model No.: ARNU093TNC2

Cooling: 2.8 kW

Heating: 3.2 kW

Consult your Rep for pricing

PRODUCT SUPPORT

The four way cassette discharges in four directions. One unit placed in center can accommodate most rooms. The four way is ceiling mounted and includes it's own filter system.

 Operation

  • Auto changeover (Heat Recovery only)
  • Auto operation
  • Auto restart
  • Child lock 
  • Dual thermistor control 
  • Forced operation
  • Group control
  • High ceiling
  • Hot start
  • Self diagnostics 
  • Sleep mode 
  • Timer (on/off)
  • Weekly schedule 
  • Soft dry (dehumidification) 

Airflow

  • Auto direction/swing (up/down) 
  • Fan speed control
  • Chaos wind (random fan speed)
  • Swirl wind (alternating vanes)
  • Jet cool (fast cooling) 

Filter

  • Washable pre-filter
  • Plasma 

Controllers

  • 7-day programmable controller 
  • Simple controller with mode
  • Simple controller without mode
  • Wireless handheld controller

Other

  • Condensate lift1
  • Ventilation (outside air)²
  • Side branch ducting³
  • Standard grill4
  • Auto elevation grill kit5
  • Corner access panels

1: 27 ½ inches from bottom of unit

2: Ventilation kit required for 24-48 MBh PTVK410 and PTVK420 

Temperature, humidity, and volume limitations apply

See Engineering Manual for static pressure requirements and condition limits

3: See Engineering Manual for airflow and static pressure requirements

4: Standard grill is a required option (PT-UQC for 7-18MBh/ PT-UMC for 24-48MBh)

5: Available only with 24-48 MBh

Model   ARNU093TNC2

Capacity

Cooling

Btu/h

9,600

kW

2.8

Heating

Btu/h

10,900

kW

3.2

Power Input

Cooling

W

144

Heating

W

144

Power Supply

V / Hz / ø

208-230 / 60 /  1

Dimensions(W×D×H)3

Body

inch

33.0 x 33.0 x 9.7

Grille

inch

37.4 x 37.4 x 1

Weight

Body

lbs

52

Grille

lbs

10

Sound Pressure (H/M/L)4

dB(A)

30/26/22

Air Flow Rate (H/M/L)

CFM

484/424/364

Note :
1. Capacities are based on the following conditions
    Cooling-Indoor temp. 80°F DB / 67°F WB           Heating-Indoor temp. 70°F DB
    Outdoor temp. 95°F DB                               Outdoor temp. 47°F DB / 43°F WB
    Interconnecting Piping Length 25ft   Level Difference of 0ft
2. Capacities are net capacities
3.  Dimensions are for casing only and do not include hangers, control boxes, and pipes. See engineering manual for detail dimensions.
4. Sound pressure levels as tested in an anechoic chamber under ISO Standard 1996.
5. Due to our policy of innovation some specifications may be changed without notification.

Download Type Category Product Name Model No.
Download Submittals Discontinued Ceiling Cassette - Four-way ARNU093TNC2